Model | EKRV040A1/AR1 | EKRV050A1/AR1 | EKRV060A1/AR1 | EKRV050A1/AR1 | EKRV060A1/AR1 | EKRV070A1/AR1 | EKRV080A1/AR1 | EKRV100A1/AR1 | EKRV120A1/AR1 | EKRV140A1/AR1 | ||
Nominal Cooling Capacity | kw | 10 | 12.5 | 15 | 12.5 | 15 | 19 | 25 | 28 | 33.5 | 40 | |
Nominal Heating Capacity | kw | 11.5 | 14 | 17 | 15 | 17.5 | 21 | 28 | 31.5 | 37 | 44 | |
Input power | Cooling | kw | 3.3 | 4.1 | 4.9 | 4.1 | 4.6 | 5.9 | 7 | 7.8 | 9.5 | 11.1 |
Heating | kw | 3 | 3.8 | 4.2 | 3.8 | 4.2 | 5.8 | 6.7 | 7.6 | 9.2 | 10.8 | |
Power supply | v/ph/hz | 220/1/50 | 380/3/50 | |||||||||
Rated current |
Cooling | A | 15 | 18.6 | 22.3 | 7.9 | 8.7 | 12.2 | 14.8 | 16.4 | 18.3 | 21.4 |
Heating | A | 13.6 | 17.3 | 19.1 | 7.2 | 8.3 | 12 | 13.6 | 15.1 | 17.4 | 20.9 | |
Connector size |
Liquid pipe | mm | 9.52 | 9.52 | 9.52 | 9.52 | 9.52 | 9.52 | 9.52 | 9.52 | 12.7 | 12.7 |
Gas pipe | mm | 15.88 | 15.88 | 15.88 | 15.88 | 15.88 | 15.88 | 22.2 | 22.2 | 22.2 | 28.6 | |
Unit weight | kg | 120 | 125 | 129 | 125 | 129 | 135 | 290 | 300 | 305 | 350 | |
Noise | dB(A) | 59 | 59 | 60 | 59 | 60 | 61 | 56 | 57 | 60 | 60 | |
Refrigerant type | R410A | |||||||||||
Dimensions (W x D x H) | mm | 970x355x1050 | 970x355x1255 | 970x355x1050 | 970x355x1255 | 990x840x1840 | 1290x840x1840 | |||||
Model | EKRV160A1/AR1 | EKRV180A1/AR1 | EKRV200A1/AR1 | EKRV220A1/AR1 | EKRV240A1/AR1 | EKRV260A1/AR1 | EKRV280A1/AR1 | EKRV300A1/AR1 | EKRV320A1/AR1 | EKRV340A1/AR1 | ||
Nominal Cooling Capacity | kw | 45 | 50.5 | 56 | 61.5 | 68 | 73 | 78.5 | 85 | 90 | 95.5 | |
Nominal Heating Capacity | kw | 49.5 | 56 | 61 | 68 | 73 | 81 | 86.5 | 93.5 | 99 | 105.5 | |
Input power | Cooling | kw | 12.9 | 14.6 | 15.5 | 17.3 | 19.2 | 20.7 | 22.4 | 24 | 25.8 | 27.5 |
Heating | kw | 12.5 | 14 | 14.6 | 16.6 | 18.1 | 20.1 | 21.7 | 23.3 | 25 | 26.5 | |
Power supply | v/ph/hz | 380/3/50 | ||||||||||
Rated current |
Cooling | A | 24.1 | 28.7 | 31.3 | 34.9 | 37.3 | 39.7 | 42.4 | 46.8 | 50.3 | 52.8 |
Heating | A | 23.8 | 27.7 | 30.8 | 33.2 | 35.1 | 38.3 | 42.2 | 45.3 | 49 | 52.5 | |
Connector size |
Liquid pipe | mm | 12.7 | 12.7 | 15.88 | 15.88 | 15.88 | 15.88 | 15.88 | 15.88 | 19.05 | 19.05 |
Gas pipe | mm | 28.6 | 28.6 | 28.6 | 28.6 | 28.6 | 34.9 | 34.9 | 34.9 | 34.9 | 34.9 | |
Equalizer pipe size | mm | -- | -- | -- | -- | -- | 9.52 | 9.52 | 9.52 | 9.52 | 9.52 | |
Unit weight | kg | 360 | 370 | 590 | 590 | 600 | 655 | 665 | 710 | 720 | 730 | |
Noise | dB(A) | 60 | 61 | 61 | 62 | 62 | 62 | 62 | 62 | 63 | 63 | |
Refrigerant type | R410A | |||||||||||
Dimensions (W x D x H) | mm | 1290x840x1840 | 1990x840x1840 | 2280x840x1840 | 2580x840x1840 | |||||||
Model | EKRV360A1/AR1 | EKRV380A1/AR1 | EKRV400A1/AR1 | EKRV420A1/AR1 | EKRV440A1/AR1 | EKRV460A1/AR1 | EKRV480A1/AR1 | EKRV500A1/AR1 | ||||
Nominal Cooling Capacity | kw | 101 | 108 | 113 | 118.5 | 124 | 129.5 | 136 | 141 | |||
Nominal Heating Capacity | kw | 112 | 117 | 122.5 | 129 | 134 | 141 | 146 | 152 | |||
Input power | Cooling | kw | 29.2 | 30.3 | 32.1 | 32.7 | 34.7 | 36.5 | 38.4 | 40.2 | ||
Heating | kw | 28 | 28.9 | 30.6 | 32.1 | 32.7 | 34.7 | 36.2 | 38.1 | |||
Power supply | v/ph/hz | 380/3/50 | ||||||||||
Rated current |
Cooling | A | 57.4 | 58.7 | 61.5 | 66 | 68.6 | 72.2 | 74.7 | 78.2 | ||
Heating | A | 55.4 | 56 | 59.9 | 62.8 | 65.9 | 68.3 | 70.2 | 73.9 | |||
Connector size |
Liquid pipe | mm | 19.05 | 19.05 | 19.05 | 19.05 | 19.05 | 19.05 | 19.05 | 19.05 | ||
Gas pipe | mm | 34.9 | 41.3 | 41.3 | 41.3 | 41.3 | 41.3 | 41.3 | 41.3 | |||
Equalizer pipe size | mm | 9.52 | 9.52 | 9.52 | 9.52 | 9.52 | 9.52 | 9.52 | 9.52 | |||
Unit weight | kg | 740 | 950 | 960 | 970 | 1190 | 1190 | 1200 | 1200 | |||
Noise | dB(A) | 63 | 64 | 64 | 64 | 65 | 65 | 65 | 65 | |||
Refrigerant type | R410A | |||||||||||
Dimensions (W x D x H) | mm | 2580x840x1840 | 3280x840x1840 | 3980x840x1840 | ||||||||
Notes: 1. The preceding cooling capacity is measured when the indoor dry/wet bulb reads 27°C/19°C, and the outdoor dry/wet bulb reads 35°C/24°C. 2. The preceding heating capacity is measured when the indoor dry/wet bulb reads 20°C/15°C, and the outdoor dry/wet bulb reads 7°C/6°C. 3. In the preceding table, heating capacity* is only applicable to heat pump units, and is omitted for cooling-only units. 4. For details about on-site power distribution and wiring for unit installation, see the nameplate or installation manual of the unit. 5. The noise levels are measured in a semi-silent room by averaging the noise levels at four sides of the unit. The checkpoints are 1 meter away from the unit at a height of (unit height + 1 meter)/2. In actual environment, the operation noise of the unit is generally higher due to ambient noise. |